MIGRATE


Project Description

Our future energy supply will come from various sources located at smaller or greater distances from consumer centres. These will be connected at different voltage levels and increasingly with the help of various power electronic converter technologies. This entails a fundamental change in the structure and topology of the generation, transmission and distribution of electric power systems. Project MIGRATE takes a look ahead to the year 2040 and identifies major operational challenges for such a system.

Conventional power systems have a unique characteristic the large mass of conventional generators creates system inertia. In case of faults, large system inertia prevents the quick acceleration of the generators and gives more time for the protection to eliminate the fault. In the future, a great amount of conventional power production will be replaced by renewable resources, e.g. wind and solar power This means that more power electronics will be applied to connect these renewable sources to the system, convert DC to AC and vice versa, as well as control voltage and frequency variations for various power sources. Because of the low mass of wind generators, future power systems will have lower inertia levels. For over a hundred years we have been depending on system inertia for a stable system and a secure power supply Now, we need to completely rethink our protection and control strategies. This is even more complex because we have to resolve this while the system is in transition, with variable renewable resources being integrated, and conventional ones decommissioned.

Research

Reliable fault detection and protection algorithms are an important subject of this project. Current protection schemes are designed for one-directional currents. With a high penetration of renewable energy such as local solar power generation, fault currents become bi-directional. Besides, with lower amplitudes, fault currents will be harder to distinguish from normal load currents. Furthermore, as generators will have low inertia, the critical clearing time (which is a measure for losing synchronism) may significantly decrease. Therefore, faults should be removed more quickly.For a large part, the research is fundamental, as we are trying to understand how a whole new kind of inverter-based system can be monitored, controlled and protected. This involves the development of novel research approaches and methodologies From a practical point of view, proposed solutions cannot always be implemented immediately. Therefore, investigating how far existing technologies and regulations can contribute to risk assessment and system security is also part of the project. This will result in recommendations to European Transmission System Operators.

PARTNERS

MIGRATE has 24 partners which include twelve universities and twelve European TSOs. TenneT TSO is the project coordinator The project name is derived from the research topic "Massive InteGRATion of power Electronic devices". MIGRATE forms part of the EU's Horizon2020 framework programme for research and innovation.

V. Sewdien

Vinay Sewdien received his Masters of Science in Electrical Engineering from KU Leuven  and TU Delft. After his graduation, Vinay started at TenneT TSO, the Dutch electricity transmission system operator, and worked on topics such as wide area measurement systems and power system stability. Since January 2016 Vinay started to pursue his PhD degree from the Delft University of Technology under the MIGRATE project. Vinay is the Technical Secretary of the international CIGRE study committe C2 on System Operations and Control. Furthermore, he is a member of CIGRE joint working groups C2/C4.37 and C2/B4.38 and of IEEE PES.

For further information, please contact:


Project Team:

An energy system in transition is like flying in an airplane whilst changing components during the flight and still keeping the airplane up in the air

Prof.ir. Mart van der Meijden

Key Publications

  1. J. Chavez, M. Popov, A. Novikov, S. Azizi and V. Terzija: Protection Function Assessment of Present Relays For Wind Generator Applications, International Conference on Power System Transient, Perpignan, 2019.
  2. M. Popov, J. Chavez at.al: Low Latency Stockwell Transform Based Secured Distance Protection Scheme for Power Network Connected with High Renewable Penetration, PAC World, Bulgaria, 2018.
  3.  G. Liu, S. Azizi, M. Sun, M. Popov and V. Terzija, "Performance of out-of-step tripping protection under renewable integration," in The Journal of Engineering, vol. 2018, no. 15, pp. 1216-1222, 10 2018.